Jin Yunyu,Chang Sainan,Zhu Lili,et al.Research on waste heat recovery and utilization technology of disinfection supply center[J].Sterile Supply,2022,01(02):47-54.
DOI:
Jin Yunyu,Chang Sainan,Zhu Lili,et al.Research on waste heat recovery and utilization technology of disinfection supply center[J].Sterile Supply,2022,01(02):47-54. DOI: 10.11910/j.issn.2791-2043.2022.2.03.
Research on waste heat recovery and utilization technology of disinfection supply center
Objective,2,This paper explores the waste heat recovery and reuse technology of condensate in disinfection supply center.,Methods,2,Through theoretical analysis and practical comparison, the recovery of equipment drainage and steam condensate was quantitatively analyzed. According to the actual layout of hospital buildings, the recovery schemes of condensate cooling season and heating season were designed.,Results,2,The waste heat recovered from condensate provides sanitary hot water, and the make-up water is heated to 60 °C at 20 °C. The recovered heat is 185.8 kW, the refrigeration capacity of chilled water is 38.5 kW, and the heating.,Conclusion,2,Capacity of heating circulating water is 93.5 kW. The total annual economic benefit can reach 620000 yuan, and the coal consumption can be saved 288 t/year.
关键词
Keywords
Steam condensateEquipment energy consumptionCondensate recoveryThermal economic benefits
references
Opinions on completely, accurately and comprehensively implementing the new development concept and doing a good job in carbon peak and carbon neutralization
WS310-2016 :Central sterile supply department(CSSD)-Part1:Management standard
Md Mayeedul Islam and Thunyaluk Pojtanabuntoeng and Rolf Gubner. Condensation corrosion of carbon steel at low to moderate surface temperature and iron carbonate precipitation kinetics[J]. Corrosion Science, 2016, 111 : 139-150.
Yanwen Wu, The Architecture and Application of a New Type High Temperature Condensate Closed-Recovery System [J]. Key Engineering Materials 2010.7
Suying Wu, Condensate recovery system applications and problem solving [J] , Equipment Management and Maintenance 2008. 10.
Debabrata Basu. Reason behind wet pack after steam sterilization and its consequences: An overview from Central Sterile Supply Department of a cancer center in eastern India[J]. Journal of Infection and Public Health, 2017, 10(2) : 235-239.
Holdsworth Jill. Targeting Zero—preventing Surgical Site Infections by Reducing Immediate Use Steam Sterilization (IUSS) of Surgical Instruments[J]. AJIC: American Journal of Infection Control, 2021, 49(6S) : S5-S5.
Milan Kubín and Jiří Hirš. Clean Steam from a Plate-Type Exchanger of a Steam Generator for Medical Facilities[J]. Advanced Materials Research, 2014, 3604(1052-1052) : 308-311.
Global Washer Disinfector Market Size, Share and Analysis Report 2015: Radiant Insights, Inc[J]. M2 Presswire, 2015,